Operating Temp : | -10°c to max.+90°C |
---|---|
Nominal voltage : | 1.1 KV |
Test voltage : | 3.0 KV |
Min. bending radius : | 6 x cable Diameter |
Standard Packing: | Coils 100, 200,300, 500, 1000m |
---|
As per IS: 694:2010 | Red, Yellow, Blue |
---|---|
As per IEC:60227 | Black, Blue, Brown. |
Conductor | Insulation | Sheath | Conductor Resistance at 20°C (max) | Current Rating at 40°C | ||||
---|---|---|---|---|---|---|---|---|
Size of Cable | No. of Wire / Size of Wire | Thickness | Core OD | Thickness | Overall Size | |||
Thickness | Width | |||||||
Sq. mm. | Nos./mm | mm | mm | mm | mm | mm | Ω/km | Amps. |
1.5 | 22/0.30 | 0.8 | 3.25 | 1.15 | 6.0 | 12.8 | 12.1 | 14 |
2.5 | 36/0.30 | 0.9 | 3.84 | 1.15 | 6.4 | 14.6 | 7.41 | 18 |
4.0 | 56/0.30 | 1.0 | 4.5 | 1.15 | 7.4 | 16.8 | 4.95 | 26 |
6.0 | 84/0.30 | 1.0 | 5.3 | 1.15 | 7.9 | 18.7 | 3.30 | 31 |
10.0 | 140/0.30 | 1.0 | 6.5 | 1.4 | 9.9 | 23.7 | 1.91 | 42 |
16.0 | 224/0.30 | 10. | 8.0 | 1.4 | 11.4 | 28.0 | 1.21 | 57 |